A Study on Improvement of Test Method of Nuclear Power Plant ESF ACS by applying Regulatory Guide 1.52 (Rev.3)
* 본 문서는 배포용으로 복사 및 편집이 불가합니다.
서지정보
ㆍ발행기관 : 한국방사성폐기물학회
ㆍ수록지정보 : 방사성폐기물학회지 / 8권 / 4호
ㆍ저자명 : Sook-Kyung Lee, Kwangsin Kim, Soon Hwan Sohn, Kyu-Min Song, Kaewoo Lee, Jeong-Seo Park, Byoung Ho Cho, Byeang Jea Yoo, Soon Joon Hong, Sun Haeng Kang
ㆍ저자명 : Sook-Kyung Lee, Kwangsin Kim, Soon Hwan Sohn, Kyu-Min Song, Kaewoo Lee, Jeong-Seo Park, Byoung Ho Cho, Byeang Jea Yoo, Soon Joon Hong, Sun Haeng Kang
목차
Abstract 요약 I. 서론 II. 연구방법 가. ESF 공기정화계통 현황 파악 및 실험장치 제작 나. 활성탄 습분탈착 실험 다. DOP 대체시험물질 비교실험 라. 활성탄 성능시험 131I 투과허용율 변경 검토 III. 결과 및 고찰 가. 영광 5,6호기 ESF 공기정화계통 운영 현황 나. 활성탄 습분탈착 다. HEPA 필터 현장누설 시험물질 변경 라. 활성탄 성능시험 투과허용율 기준 변경 IV. 결론 참고문헌한국어 초록
공학적 안전설비 공기정화계통의 규제지침인 Reg. Guide 1.52(Rev.3)의 변경사항중 성능시험과 관련 한 운전가능성 시험시간 단축, HEPA 필터 현장누설시험용 시험물질 변경 및 활성탄 성능시험 Methyl Iodidie 투과허용율 상향 변경을 영광 5,6호기에 적용하고자, 모사실험장치와 현장 설비를 활용하여 기술 적 타당성을 확인하는 실험을 수행하였다. 10시간 이상의 장시간 운전가능성 시험을 통해 계통내 습분을 제거하여도 시험후 1∼4일만에 회복됨을 확인하여 운전가능성 시험은 기기적 운전가능성 점검에 적합한 매월 15분 이상의 시험을 수행하는 것이 타당함을 확인하였다. HEPA 필터 현장누설시험용 시험물질 변 경을 위해 DOP와 PAO의 에어로졸 입자크기, 발생량, 누설인지도를 비교한 결과 PAO는 원전에서도 DOP 대체시험물질로 사용 가능함을 확인하였다. 베드깊이 4 인치 이상의 활성탄여과기에 대한 Methyl Iodide의 투과율 허용치가 0.175 %에서 0.5 %로 상향 변경된 것은, ASTM D3803(1989)으로의 활성탄 성 능시험 방법 변경에 따른 것으로서, 30 ℃ 상대습도 95 %에서의 Methyl Iodide 투과허용율 0.5 %가 사용 중 활성탄의 성능을 시험하기에 충분히 보수적인 시험방법임을 확인하였다. 본 실험 결과를 바탕으로 영 광 5,6호기는 인허가변경을 완료하였다.영어 초록
U. S. NRC Regulation Guide 1.52 regulating ESF ACS in nuclear power plants has been revised to revision 3. To apply reduction of operability test time, allowance of alternative challenge agents for in-place leak test of HEPA filters, and upgrade of Methyl Iodide penetration acceptance criterion in activated carbon performance test suggested in Reg. Guide 1.52(Rev.3) on Yonggwang units 5 and 6 ESF ACSes, technical feasibility study was carried out with on-site experiments as well as experiments with a lab-scale model. It was confirmed that the moisture in the system returned to the level before the test in 1 or 4 days even though the moisture was removed during the operability test lasting more than 10 hours. Therefore, it is appropriate to perform monthly operability test in 15 minutes just long enough to check the operability of equipment. To change challenge material for in-place HEPA filter leak test, size of aerosol, production rate, and leak detection capability were compared for DOP and PAO. It was concluded that PAO can be substituted for DOP in nuclear power plants. The upgrade of Methyl Iodide penetration acceptance criterion from 0.175 % to 0.5 % in active carbon filter bed deeper than 4 inches was to conform to the change of activated carbon performance test method to ASTM D3803(1989). It was confirmed that Methyl Iodide penetration acceptance criterion of 0.5 % under 30 ,relative humidity 95 % condition was conservatively good enough for testing performance of active carbon insitu. The licence change of Yonggwang units 5 and 6 has been completed based on this study.참고 자료
없음태그
"방사성폐기물학회지"의 다른 논문
- 방사성폐기물학회지 논문 투고요령3페이지
- Source Term Characterization for Structural Components ..7페이지
- Assessment of Potential Impacts of the Proposals for Mu..8페이지
- Soil-to-Rice Seeds Transfer Factors of Radioiodine and ..9페이지
- A Study on Construction and Application of Nuclear Grad..9페이지
- Recovery of Residual LiCl-KCl Eutectic Salts in Radioac..7페이지
- Assessment on the Monitoring System for KURT using Opti..9페이지
- Study on the Geological Structure around KURT Using a D..13페이지
- Multilateral Approaches to the Back-end of the Nuclear ..9페이지
- A Study on the Fabrication of Uranium-Cadmium Alloy and..7페이지